Introducing GC series for medium scale applications.
We are committed to provide best in class products for making Gas Detection Simple.
GC series can be used in following applications:
Flammable Gas Leak Detection: To monitor flammable gases & compounds, vapours, solvents etc in industrial plants,before they reach to potentially hazardous level i.e % Lower explosion limit. GC series in combination of any third party gas detection equipment, activates alarm & alerts the control room for further actions.
Oxygen monitoring: GC series has inbuilt programs & settings to interface Oxygen monitoring transmitters. Alarm logic for rising & falling type of alarm activation are available to set up levels for Oxygen deficiency & enrichment.
Toxic Gas Leak Detection : To monitor presence of Toxic gases present in the workplace to save human workforce working in plants & shop floors. Alarm levels can be set up as per the regulated guidelines of regulatory bodies. Full scale range setting in toxic transmitters is an important parameter, GC series makes this very simple by providing manual data entry field to set the full scale range of the toxic gas detector, its so simple..
VOC measurements: As one of the important parameter of industrial hygiene compliance, GC series can be used to interfaced with PID type VOC measuring transmitters. Alarm levels can be set as per the VOC & monitoring as well as data-logging is possible.
GC-6
GC Series, GC-06 supports 1 to 6 channel Gas leak detection systems. Compact size allows installation with smaller footprint.
Operating voltage: 230VAC-Single phase-50Hz
Cabinet dimensions: H460mm x W350mm x D200mm
Removable gland plate : Bottom
Gas detector Inputs : 6 x 4-20mA analog
Gas detector supply : 24VDC-5Amp
2-wire / 3-wire detectors are supported
Gas detector full scale range can be set as per the range of gas detector. Common set point for detector Fault condition, this is factory set. Common set point for detector Warning condition, this is factory set. Individual set point for alarm- 1 level.
Individual set point for alarm-2 level. Optional Separate potential free SPDT contact for alarm-1 level of every channel. 2 nos 24VDC output : Common for external Strobe at Alarm -1.
2 nos 24VDC output : Common for external horn at Alarm -2.
1 nos Potential free SPDT contact: Common for alarm-1.
1 nos Potential free SPDT contact: Common for alarm-2.
GC-12
GC Series, GC-12 supports 1 to 12 channel Gas leak detection systems. Multiple outputs makes it a perfect choice for complex & critical applications like BMS.
Operating voltage: 230VAC-Single phase-50Hz
Cabinet dimensions: H450mm x W450mm x D250mm
Removable gland plate : Bottom
Gas detector Inputs : 12 x 4-20mA analog
Gas detector supply : 24VDC
2-wire / 3-wire detectors are supported
Gas detector full scale range can be set as per the range of gas detector. Common set point for detector Fault condition, this is factory set. Common set point for detector Warning condition, this is factory set. Individual set point for alarm- 1 level.
Individual set point for alarm-2 level. Optional Separate potential free SPDT contact for alarm-1 level of every channel. 2 nos 24VDC output : Common for external Strobe at Alarm -1.
2 nos 24VDC output : Common for external horn at Alarm -2.
1 nos Potential free SPDT contact: Common for alarm-1.
1 nos Potential free SPDT contact: Common for alarm-2.
GC-18
GC Series, GC-18 supports 1 to 18 channel Gas leak detection systems. Best choice for applications involving Food & Beverages, Small chemical plant module, Single floor sized research lab and many more..
Operating voltage: 230VAC-Single phase-50Hz
Cabinet dimensions: H600mm x W600mm x D250mm
Removable gland plate : Bottom
Gas detector Inputs : 18 x 4-20mA analog
Gas detector supply : 24VDC-10 Amp
2-wire / 3-wire detectors are supported
Gas detector full scale range can be set as per the range of gas detector. Common set point for detector Fault condition, this is factory set. Common set point for detector Warning condition, this is factory set. Individual set point for alarm- 1 level.
Individual set point for alarm-2 level.
2 nos 24VDC output : Common for external Strobe at Alarm -1.
2 nos 24VDC output : Common for external horn at Alarm -2.
1 nos Potential free SPDT contact: Common for alarm-1.
1 nos Potential free SPDT contact: Common for alarm-2.
GC-Flameproof
Flameproof GC Series supports GC-6/12/18 channel Gas leak detection systems. Best choice for applications involving Food & Beverages, Small chemical plant module, Single floor sized research lab and many more..
GC Series is backed up by its powerful Application software & Programs, which make them the best choice for your Gas Detection Systems.
GC Series controllers are integrated in a Exd (Flameproof) cabinets. HMI shall be operated using front facia push buttons. Compact design allows power packed performance & smaller footprints.
CMRI CERT NO: IN/CIMFR/TR20/3372
Enclosure: IS/IEC 60079-1-2014 Gas Group IIA & IIB Area Classification: Zone 1 & 2 as per IEC 60079-0
Gas Group: IIA & IIB as per IS/IEC 60079-1-2014
Degree of Protection: IP65 as per IS/IEC 60529-2001 Material of Construction: LM6 Aluminium
Temperature Class : T6 as per IS/IEC 60079-0-2017 Dust Ignition Protection: “t” as per IS/IEC 60079-3: 2013 Rating: 20AMP 230Volts
Earthing : 1 nos inside / 2 nos Outside
Finish: RAL7035, Powder Coated